MENU
|
/DEV
|
/MAX
|
INPT
INPUT
TYPE
|
Show
input choices:
|
Input
Type J.TC Iron vs. Constantan (NIST)
K.TC Chromel vs. Alumel (NIST)
DJ.TC Iron vs. Copper (DIN)
T.TC Copper vs. Copper-Nickel
|
DEC.P
Decimal Point
|
Show
decimal point position
|
FFFF.
FFF.F
|
RD.CF
Reading Configuration
|
R.1
|
C: Celsius
F: Fahrenheit
|
S1.CF
SETPOINT 1 CONFIGURATION
|
S.1
S.2
|
A: Active above
B: Active below
U: Unlatched
L: Latched
|
S2.CF
SETPOINT 2 CONFIGURATION
|
S.1
S.2
|
A: Active above
B: Active below
U: Unlatched
L: Latched
|
S1.DB
SETPOINT
1 DEADBAND
|
Scroll
right one digit
|
Change flashing digit's value |
S2.DB
SETPOINT
2 DEADBAND
|
Scroll
right one digit
|
Change flashing digit's value |
Output
Configuration Analog Output
|
0.1
0.2
0.3
0.4
0.5
|
D: Disabled
E: Enabled
V: Voltage analog out
C: Current analog out
A: Retransmission of temperature
P: Proportional to error
D: Proportional analog output is direct reading
R: Proportional analog output is reverse acting
F: 0-10 V proportional
H: 0-5 V proportional |
Notes
* If you select 0.2=V, you may select your analog output to
be 0-10 V or 0-5V by accessing sub-menu 0.5=F or 0.5=H
* If 0.3=P, you may select your proportional output analog
to be direct 0.4=D (4-20 mA), (0-5V), (0-10v) or reverse acting
0.4=R (20-4 mA), (5V-0V), (10V-0V). |
P.BND
Proportional Band
|
Show
prior value entered
|
Change flashing digit's value |
M.RST
Manual Reset
|
Show
prior value entered
|
Change flashing digit's value |
OT.S.O
Output Scale/Offset
Enter new value & show "OUT1"
Enter new value & show "RD 2"
Enter new value & show "OUT2"
|
Show
"RD 1" & prior value
Scroll right one digit
Show prior value
Scroll right one digit
Show prior value
Scroll right one digit
Show prior value
|
Change flashing digit's value
Change flashing digit's value
Change flashing digit's value
Change flashing digit's value |
C.J.OF
Cold Junction Offset
|
Show actual or prior value
|
Change
flashing digit's value (░C only) |
LK.CF
Lock Out Configuration
|
RS=
SP=
L3=
|
E (Enable RESET button in run mode)
D (Disable RESET button in run mode)
E (Enable setpoint changes)
D (Disable setpoint changes)
0 (SETPTS button display setpoint values)
1 (SETPTS button display software "v.-03"
version) |